Liebert NX is a mid-sized, three-phase uninterruptible power supply (UPS) system that delivers complete, centralized data center power protection. Emerson 10-30KVA User Manual. Download 3.14 Mb. For Business-Critical Continuity. The Liebert NX™ UPS is designed primarily for telecommunications and data processing applications. Liebert Corporation neither recommends nor knowingly sells this product for use with life support and other designated “critical” devices.

Advertising

UPS Status Messages

99

Inverter Contactor Fail

The Inverter contactor has failed.

This alarm is triggered when the feedback signal and the state of the contactor is not identical for

a specified time. Contact Liebert Global Services at 800-543-2378 for assistance.

Output Fuse Fail

At least one of the output fuses is open. Contact Liebert Global Services at 800-543-2378 for

assistance.

Control Power 2 Fail

Control Power 2 is abnormal or lost. Contact Liebert Global Services at 800-543-2378 for

assistance.

Unit Overload

The UPS is confirmed to be overload when the load arises above 105% nominal rating.

The alarm automatically resets once the overload condition is removed.

1. Confirm that the alarm is true by checking the load percent indicated on the LCD panel to

determine which phase is being overloaded.

2. If the alarm is true, measure the actual output current to verify that the indications are valid.

Disconnect unnecessary load and ensure the safety. In a parallel system, a severe load

sharing error can also leads to the alarm.

Contact Liebert Global Services at 800-543-2378 for assistance.

System Overload

The UPS parallel system is confirmed to overload when the total load arises above 105% nominal

rating for the set basic number of UPSs. The alarm automatically resets once the overload

condition is removed.

1. Confirm that the alarm is true by checking the system load percent indicated on the LCD

panel to determine which phase is being overloaded.

2. If the alarm is true, measure the actual output current to verify that the indications are valid.

Disconnect unnecessary load and ensure the safety. In a parallel system, a severe load

sharing error can also leads to the alarm.

Unit Overload Timeout

The UPS is confirmed to overload and the overload times out.

Liebert Nx Ups

Note 1: the highest loaded phase will indicate overload timing-out first.

Note 2: When the timer is active then alarm “unit overload” should also be active as the load is

above nominal.

Note 3: When the timer has expired, the inverter Static Switch is opened and the load transferred

to bypass. The inverter shutdown and will restart after 10 seconds.

Note 4: If the load decreases lower than 95% after 5 minutes, the system will transfer back to

inverter mode.

Liebert Nx 40kva Ups

Confirm that the alarm is genuine by checking the load percent indicated on the LCD. If an

overload is indicated then check the load, and investigate any additional load connected prior to

the alarm (if applicable).

Inverter Overcurrent

The current of inverter IGBT is over limit. If the fault will not reset, contact Liebert Global Services

at 800-543-2378 for assistance.

Liebert nx 40kva ups

Bypass Phase Reversed

The phase sequence direction of bypass voltage is reversed.

Normally, the phase of phase B lags 120 degrees behind phase A, and the phase of phase C lags

120 degrees behind phase B.

Verify that the phase rotation of the bypass supply presented to the UPS is correct, and rectify it if

it is found to be in error. Contact Liebert Global Services at 800-543-2378 for assistance.

Load Impact Transfer

A transfer to bypass occurred due to a large step load. The UPS should recover automatically.

Turn on connected equipment in sequential order to reduce the step loading of the inverter.

Transfer Timeout

The load is on bypass power due to excessive number of transfers that occurred within the last

hour.

The UPS will recover automatically and will transfer the load back to inverter power within an

hour.

Load Sharing Fault

UPS working within a parallel system are not sharing load current correctly. Contact Liebert

Liebert Nx 20kva

Global Services at 800-543-2378 for assistance.

DC Bus Abnormal

Shut off inverter due to abnormal DC bus voltage.

Contact Liebert Global Services at 800-543-2378 for assistance.

System Transfer

The whole paralleled UPS system transferred to bypass at the same time. This message will

Manual

appear on the UPS which passive transfer to bypass.

Parallel Board Fault

Parallel board is not working correctly. Contact Liebert Global Services at 800-543-2378

for assistance.

Table 44

Liebert Nx 30 Kva Manual

UPS status messages (continued)

Event Message

Description / Suggested Action (if any)