Universal Electronic MiniZone Panel. MiniZone EMM-3U Control Panel pdf manual download. Control Panel Honeywell Accenta User Manual. Honeywell security accenta/optima (25 pages). Mount the thermostats in each zone of the living space the thermostat has a common terminal, it is wired to C on the panel, see Fig. The Mastertrol® Mini-Zone™ -2 Zone Control Panel, Model MM-2, controls 2 zones on any single stage heating and cooling system. Each zone is controlled by a thermostat which operates a motorized damper in the zone duct to control the flow of conditioned air to the zone. (Up to 2 dampers may be wired to a single zone. Honeywell MiniZone EMM-3U Pdf User Manuals. View online or download Honeywell MiniZone EMM-3U Product Data.
® U.S. Registered Trademark
Copyright © 2000 Honeywell Inc. • All Rights Reserved
SCHEMATIC
MM-2 MASTERTROL®
MINI-ZONE™-2
69-1361
The Mastertrol® Mini-Zone™ -2 Zone Control Panel,
Model MM-2, controls 2 zones on any single stage
heating and cooling system. Each zone is controlled
by a thermostat which operates a motorized damper
in the zone duct to control the flow of conditioned air
to the zone. (Up to 2 dampers may be wired to a
single zone. When 3 or more dampers are required
a Slave Damper Control Relay, Model SDCR, is re-
quired.)
The Zone 1 Ther mostat requires a manual
changeover subbase with “O” and “B” terminals. The
“O” terminal must make with R when the subbase is
switched to the COOL Mode. The “B” terminal must
make with R when the subbase is switched to the
HEAT Mode. When the Zone 1 Subbase in either the
Heat or Cool Mode, either zone thermostat can call
for the respective mode. The zone thermostat will en-
ergize it’s zone relay which activates the heating or
cooling controls, opens it’s zone damper and closes
the damper to the zone that is satisfied. When both
zone thermostats are satisfied the heating (or cool-
ing) will shut off and all zone dampers will return to
their normal position. The normal position of the zone
dampers is set by the OPEN/CLOSED (O/C) slide
switch next to the motor terminals.
SYSTEM CONNECTIONS: The MM-2
System Terminals, on the far left side of
the panel, wire to the HVAC Unit. These
terminals are isolated “dry” switching con-
tacts similar to any typical thermostat.
These terminals are wired to the HVAC
Unit the same as any thermostat would,
when not using this zone control panel.
The MM-2 connections used are typically
the RC-G-Y-W terminals wired the the
HVAC Unit Control Center.
HYDRO-AIR Systems - When using the
MM-2 with a Hydro-Air System, one
which uses a hot water coil in the air han-
dler to provide heating in place of a fur-
nace, the wiring is almost similar to that
shown. In this application the Heat Re-
lay shown may be a zone valve or circu-
lator relay. The Fan must be controlled
by an Aquastat. In order to bring the fan
on when the water in the coil is heated.
This is wired independently of the MM-2
panel.
OIL FURNACES - When using the MM-2 with an Oil
Fired Furnace to provide heating, the T and T termi-
nals on the Oil Burner Primary Control must wire to
the RH and W terminals, on the left side of the MM-
2.
NOTE: Once operational the Oil Furnace contin-
ues to run when all zones are satisfied, reverse the
RH and W wires on the MM-2.
DAMPER MOTOR WIRING - This diagram shows
Trol-A-Temp’s typical power open-power closed op-
posed blade damper motors. Note the jumper wire
required on the motor terminals 2 and 5. Round
Spring Return Dampers can also be wired to the
MM-2. When using the ARD-PC, wire to the M1 and
M6 terminals. When using the ARD-PO, wire to the
M1 and M4 terminals.
ZONE THERMOSTAT WIRING - The MM-2 can be
used with several different single stage thermostats.
The wiring shown is for the following recommended
thermostats:
Zone 1 Thermostat
Zone 2 Thermostat
TRT(-W) and MCRS(-W)
TRT(-W)/T87F
T8090T1003*
T8090T1011*
T8602C
T8602D
T8601C*
T8603D*
*These thermostats may require additional wires.
Refer to the wiring information included with the ther-
mostat for complete information.
4
5
6
Z
1
2
3
X
ZONE 2 DAMPER MOTOR
T6/Y
T5/R
T4/W
4
5
6
Z
1
2
3
X
HVAC UNIT CONNECTIONS
M6
M4
M11
T6/Y
T5/R
T4/W
M6
M4
M1
O1
G1
B1
B
2
1
5/R
6/Y
4/W
Y
G
R
MASTERTROL MINI - ZONE
24 VOLT 40 VA
TRANSFOMER
MODEL PMT-40
MODEL MM-2
MODEL DPBT
(T678A)
HEAT RELAY
ZONE 2 THERMOSTAT
ZONE 1 THERMOSTAT
AND SUBBASE
M13557
Y
O
G
RC
RH
W
Y
R
W
O
G
B
C
Honeywell Universal Mini Zone Board
W
ZONE 1 DAMPER MOTOR
24 VOLT
TRANSFORMER
FAN RELAY
SYSTEM
ZONE 2
ZONE 1
O
C
O
C
R C
The Mastertrol® Mini-Zone™ -2 Zone Control Panel, Model MM-2, controls 2 zones on any single stage heating and cooling system. Each zone is controlled by a thermostat which operates a motorized damper in the zone duct to control the flow of conditioned air to the zone. (Up to 2 dampers may be wired to a single zone. When 3 or more dampers are required a Slave Damper Control Relay, Model SDCR, is required.)
The Zone 1 Thermostat requires a manual changeover subbase with “O” and “B” terminals. The “O” terminal must make with R when the subbase is switched to the COOL Mode. The “B” terminal must make with R when the subbase is switched to the HEAT Mode. When the Zone 1 Subbase in either the Heat or Cool Mode, either zone thermostat can call for the respective mode.The zone thermostat will energize it’s zone relay which activates the heating or cooling controls, opens it’s zone damper and closes the damper to the zone that is satisfied. When both zone thermostats are satisfied the heating (or cooling) will shut off and all zone dampers will return to their normal position.The normal position of the zone dampers is set by the OPEN/CLOSED (O/C) slide switch next to the motor terminals.
OIL FURNACES - When using the MM-2 with an Oil Fired Furnace to provide heating, the T and T terminals on the Oil Burner Primary Control must wire to the RH and W terminals, on the left side of the MM- 2. NOTE: Once operational the Oil Furnace continues to run when all zones are satisfied, reverse the RH and W wires on the MM-2.
DAMPER MOTOR WIRING - This diagram shows Trol-A-Temp’s typical power open-power closed opposed blade damper motors. Note the jumper wire required on the motor terminals 2 and 5. Round Spring Return Dampers can also be wired to the MM-2. When using the ARD-PC, wire to the M1 and M6 terminals. When using the ARD-PO, wire to the M1 and M4 terminals.
SCHEMATIC
ZONE THERMOSTAT WIRING - The MM-2 can be used with several different single stage thermostats. The wiring shown is for the following recommended thermostats:
Zone 1 Thermostat | Zone 2 Thermostat |
TRT(-W) and MCRS(-W) | TRT(-W)/T87F |
T8090T1003* | T8090T1011* |
T8602C | T8602D |
T8601C* | T8603D* |
*These thermostats may require additional wires. Refer to the wiring information included with the thermostat for complete information.
ZONE 1 THERMOSTAT | |||
AND SUBBASE | ZONE 2 THERMOSTAT | ||
O | Y | 5/R | |
G | R | 4/W | 6/Y |
B W |
SYSTEM CONNECTIONS: The MM-2 System Terminals, on the far left side of the panel, wire to the HVAC Unit. These terminals are isolated “dry” switching contacts similar to any typical thermostat. These terminals are wired to the HVAC Unit the same as any thermostat would, when not using this zone control panel. The MM-2 connections used are typically the RC-G-Y-W terminals wired the the HVAC Unit Control Center.
HYDRO-AIR Systems - When using the MM-2 with a Hydro-Air System, one which uses a hot water coil in the air handler to provide heating in place of a furnace, the wiring is almost similar to that shown. In this application the Heat Relay shown may be a zone valve or circulator relay. The Fan must be controlled by an Aquastat. In order to bring the fan on when the water in the coil is heated. This is wired independently of the MM-2 panel.
MODEL DPBT (T678A)
Honeywell Universal Mini Zone Installation Manual
Y
G
FAN RELAY
C R
24 VOLT TRANSFORMER
W
HEAT RELAY
HVAC UNIT CONNECTIONS
Honeywell Minizone Instruction Manual
MASTERTROL MINI - ZONE | MODEL MM-2 | |||||||
SYSTEM | ||||||||
Y | O1 | T6/Y | T6/Y | |||||
O | G1 | T5/R | T5/R | |||||
G | B1 | T4/W | T4/W | |||||
RC | B | M6 | C | M6 | C | |||
RH | 2 | M4 | O | M4 | O | |||
W | 1 | ZONE 1 | ZONE 2 | |||||
M1 | M11 | |||||||
4 | 5 | 6 | Z | 4 | 5 | 6 | Z | |
R C | 1 | 2 | 3 | X | 1 | 2 | 3 | X |
24 VOLT 40 VA | ||||||||
TRANSFOMER | ||||||||
MODEL PMT-40 | ZONE 1 DAMPER MOTOR | ZONE 2 DAMPER MOTOR | ||||||
M13557 |
Honeywell Universal Mini Zone Manual
® U.S. Registered Trademark | |
Copyright © 2000 Honeywell Inc. • All Rights Reserved | 69-1361 |